Thursday, February 12, 2026
spot_imgspot_img

Top 5 This Week

spot_img

Related Posts

Ventilation Requirements (ASHRAE 62.1 & Local Codes)

1. Introduction

Ventilation requirements define the minimum outdoor air (fresh air) rates that must be supplied to occupied spaces to maintain acceptable Indoor Air Quality (IAQ).

  • ASHRAE Standard 62.1 → Global benchmark for ventilation design in commercial/institutional buildings.
  • Local Codes → Authorities in each country (Dubai Municipality, Qatar Kahramaa, Saudi SASO, Indian NBC, etc.) often adopt ASHRAE with modifications for local climate and energy goals.

2. ASHRAE 62.1 – Key Principles

ASHRAE 62.1 sets outdoor air ventilation rates based on two components:

  • Rp (People Outdoor Air Rate): L/s per person (or CFM per person) → based on occupant density.
  • Ra (Area Outdoor Air Rate): L/s per m² (or CFM per ft²) → based on building/space type.

Equation: Voz=(Rp×Pz)+(Ra×Az)V_{oz} = (R_p \times P_z) + (R_a \times A_z)Voz​=(Rp​×Pz​)+(Ra​×Az​)

Where:

  • VozV_{oz}Voz​ = Zone Outdoor Airflow
  • PzP_zPz​ = Zone population (number of people)
  • AzA_zAz​ = Zone floor area

3. Typical ASHRAE 62.1 Ventilation Rates

Space TypeRp (L/s per person)Ra (L/s per m²)Approx. ACHNotes
Office Spaces2.5 (≈ 5 CFM/person)0.3 (≈ 0.06 CFM/ft²)3–4 ACHBased on density of ~5 people/100 m²
Conference Rooms3.8 (≈ 7.5 CFM/person)0.36–8 ACHHigher occupancy → higher Rp
Classrooms (Ages 9+)5.0 (≈ 10 CFM/person)0.66–10 ACHTo maintain CO₂ <1000 ppm
Healthcare (Patient Room)5.00.66 ACH minASHRAE 170 applies in detail
Hospital Operating Room5.00.620 ACH min100% fresh air, HEPA required
Retail (Mall)3.80.36–10 ACHCrowd density factor applied
Restaurants/Dining5.00.68–12 ACHKitchen exhaust separately
LaboratoriesN/ACode-based6–12 ACHVentilation based on fume hoods
Toilets/RestroomsN/AExhaust-based10 ACH minNegative pressure required

4. Local Codes and Adjustments

  • UAE (Dubai Municipality, DM Code): Based on ASHRAE 62.1, but minimum fresh air is often 20 CFM/person in offices due to climate and energy recovery requirements.
  • Qatar (Kahramaa, Qatar Construction Standards – QCS): Follows ASHRAE but enforces stricter energy efficiency through heat recovery systems.
  • Saudi Arabia (SASO, SBC 501/502): Requires energy recovery wheels in FAHUs for high outdoor air volumes (aligning with Vision 2030 sustainability goals).
  • India (NBC, ISHRAE): Aligns with ASHRAE but defines ventilation in L/s per person with local climate emphasis.

5. Pressurization Requirements

In addition to outdoor air rates, codes specify air balance to maintain safety and comfort:

  • Positive Pressure: Offices, malls, clean rooms.
  • Negative Pressure: Toilets, kitchens, isolation rooms.
  • Neutral/Controlled Pressure: Data centers, sensitive equipment rooms.

6. Energy Efficiency Requirements

  • FAHUs handling large fresh air volumes must use energy recovery systems (heat recovery wheel, run-around coils, plate exchangers).
  • Demand-Controlled Ventilation (DCV): Required in many codes → adjusts fresh air supply based on CO₂ sensors.

7. Example Calculation (Office Zone)

  • Occupancy: 100 people
  • Zone area: 1000 m²
  • Rp = 2.5 L/s per person → 2.5×100=250 L/s2.5 × 100 = 250 \, L/s2.5×100=250L/s
  • Ra = 0.3 L/s per m² → 0.3×1000=300 L/s0.3 × 1000 = 300 \, L/s0.3×1000=300L/s
  • Total Voz=250+300=550 L/sV_{oz} = 250 + 300 = 550 \, L/sVoz​=250+300=550L/s = 1165 CFM

This fresh air requirement will then guide FAHU capacity sizing.

LEAVE A REPLY

Please enter your comment!
Please enter your name here

Popular Articles