Components of FAHU

0
21

A Fresh Air Handling Unit (FAHU) is made up of several integrated components that work together to filter, cool/heat, dehumidify, and distribute 100% fresh outdoor air into a building.


1. Casing, Panels & Insulation

  • Description: Outer body of FAHU, usually double-skin panels (inner & outer metal sheets with insulation in between).
  • Purpose:
    • Provides structural strength.
    • Prevents air leakage.
    • Reduces thermal losses and noise transmission.
  • Insulation Type: PU/PIR foam or rock wool for thermal + acoustic insulation.

2. Air Filters

  • Types:
    • Pre-Filters: Capture large dust particles.
    • Fine Filters (MERV 8–13): Remove smaller particulates.
    • HEPA Filters: Used in hospitals, labs, cleanrooms (removes >99.97% at 0.3 µm).
  • Purpose: Improves IAQ by removing dust, pollen, and microorganisms.

3. Mixing Box (Optional in Hybrid FAHU)

  • Description: Section with dampers that mixes outdoor air with return air.
  • Purpose:
    • Controls the proportion of fresh and return air.
    • Optimizes IAQ and energy consumption.
  • Note: Pure FAHUs are 100% outdoor air, but in some cases they may include a mixing box.

4. Cooling & Heating Coils

  • Cooling Coil:
    • Chilled water coil or DX coil.
    • Lowers air temperature and removes moisture (dehumidification).
  • Heating Coil:
    • Hot water, steam, or electric coil.
    • Maintains comfort in cold climates.
  • Purpose: Ensures thermal comfort and humidity control before air supply.

5. Humidifiers / Dehumidifiers

  • Humidifier: Adds moisture in dry climates.
  • Dehumidifier (via cooling coil): Removes excess humidity in hot-humid climates.
  • Purpose: Maintains recommended 40–60% RH for comfort and health.

6. Fans / Blowers

  • Type:
    • Centrifugal fans.
    • Plug fans or EC (electronically commutated) fans in modern FAHUs.
  • Purpose:
    • Move large volumes of air.
    • Overcome system static pressure (ductwork, filters, coils).
  • Control: Variable Frequency Drives (VFDs) for energy-efficient fan operation.

7. Drain Pan & Condensate Removal

  • Description: Collects condensation formed on cooling coils.
  • Purpose:
    • Prevents water carryover into ducts.
    • Drains condensate safely to waste lines.
  • Design: Corrosion-resistant, sloped for easy drainage.

8. Silencers / Acoustic Attenuators

  • Purpose: Reduce noise from fans and high-velocity airflow.
  • Application: Important in hospitals, hotels, and office spaces.

9. Control Dampers & Actuators

  • Types:
    • Fresh air dampers.
    • Return air dampers (if mixing box).
    • Exhaust/relief dampers.
  • Purpose:
    • Control airflow volume and direction.
    • Enable pressure balancing and energy efficiency.
  • Actuators: Motorized for automatic control via BMS.

10. Sensors & Control Devices

  • Types:
    • Temperature sensors.
    • Humidity sensors.
    • CO₂ sensors (for Demand-Controlled Ventilation).
    • Differential pressure sensors (for filter monitoring & pressurization).
  • Purpose: Enable real-time monitoring and automation.

11. Heat Recovery Systems (Optional)

  • Types:
    • Energy Recovery Wheel (enthalpy wheel).
    • Plate Heat Exchanger.
    • Run-around Coil.
  • Purpose: Recover cooling/heating energy from exhaust air → reduce energy consumption.
  • Mandatory: In many local codes (UAE, Qatar, Saudi) for FAHUs handling large fresh air volumes.

12. Special Hygienic Design Features (for Healthcare)

  • Antimicrobial coating on internal surfaces.
  • Smooth, cleanable interiors.
  • UV-C lamps for microbial control.
  • HEPA filter housings with airtight seals.

13. Electrical & Control Panel

  • Purpose: Controls fan motors, heaters, dampers, sensors, and communicates with BMS.
  • Features: Local operation switches, overload protection, and emergency shut-off.

14. Access Doors & Inspection Windows

  • Allow easy access for maintenance, filter replacement, and inspection.
  • Often equipped with safety latches and viewing panels.

Summary Table of FAHU Components

ComponentFunction
Casing & InsulationPrevent leakage, heat loss, and noise
Filters (Pre, Fine, HEPA)Remove dust, pollen, microbes
Mixing BoxMix fresh + return air (if hybrid FAHU)
Cooling/Heating CoilsTemperature and humidity control
Humidifiers/DehumidifiersMaintain RH (40–60%)
Fans/BlowersMove and distribute air
Drain PanRemove condensation safely
SilencersReduce noise
Dampers & ActuatorsControl airflow and pressure
SensorsMonitor IAQ, pressure, and system health
Heat Recovery DevicesImprove energy efficiency
Control PanelAutomation and BMS integration
Access DoorsMaintenance and inspection